EV Home Charger Wiring Planner

Enter your home charger's rated current, system voltage and cable run length to get the correct breaker size, wire gauge in mm² and AWG, and voltage drop. Covers single-phase Type 2 chargers (3.7 to 7.4 kW) and three-phase installations (11 to 22 kW). All EV circuits are continuous loads and are sized at 125% of rated current per IEC 60364 and NEC.

Last updated: May 2026

Select a charger preset or enter current, voltage and cable run to size your circuit.

EV chargers are continuous loads: circuits are sized at 125% of rated current (IEC 60364 / NEC 210.20).

How the EV home charger wiring planner works

Every home EV charger is classified as a continuous load because it runs at full current for 3 or more hours per session. IEC 60364 and NEC 210.20 both require that the circuit breaker and cable be sized at 125% of the charger's rated current, not 100%. The planner applies this rule automatically and then checks two independent constraints: the cable must be large enough to carry the current without overheating (ampacity), and the cable must be large enough to keep the voltage drop within your chosen limit. The correct gauge satisfies whichever constraint is stricter. If you are still choosing a charger, the cost and range tools in the EV & energy hub help you size the charging speed before you plan the wiring.

Formulas used

OutputFormula
Design currentCharger rated current (A) x 1.25
Breaker sizeNext standard IEC size at or above design current
Min. wire (single-phase)2 x rho x L x I_design / (V x drop%)
Min. wire (three-phase)sqrt(3) x rho x L x I_design / (V x drop%)
Actual voltage dropPhase factor x rho x L x I_rated / wire_area

rho = 0.0172 ohm.mm²/m (copper) or 0.0282 ohm.mm²/m (aluminium). Phase factor = 2 for single-phase, sqrt(3) for three-phase.

Common charger wiring reference

ChargerCurrentPhase / VoltageDesign currentBreaker (IEC)Min. wire Cu, 10 m, 3%
L1 US 1.9 kW16 ASingle / 120 V20 A20 A2.5 mm² (AWG 13)
EU 3.7 kW16 ASingle / 230 V20 A20 A2.5 mm² (AWG 13)
EU 7.4 kW32 ASingle / 230 V40 A40 A6 mm² (AWG 10)
UK 7.7 kW32 ASingle / 240 V40 A40 A6 mm² (AWG 10)
3-phase 11 kW16 A/phaseThree / 400 V20 A20 A2.5 mm² (AWG 13)
3-phase 22 kW32 A/phaseThree / 400 V40 A40 A6 mm² (AWG 10)

Wire sizes shown for 10 m one-way run, copper, 3% voltage drop limit. Use the planner above for your actual run length.

Installation checklist

The home charger is where the EV cost story starts

The house sets a ceiling on every number that comes after this page. Before you know what a charge costs, how long it takes, or whether a trip is feasible, you need to know what your consumer unit can actually deliver to a wallbox. That answer cascades through each tool in the sequence below:

  1. You are here: size the circuit before you choose the charger. Your consumer unit, available phases and cable run determine which charger power level is physically possible. For most Dutch and European households, 7.4 kW on a single 32 A phase is the practical ceiling without grid reinforcement. Three-phase 11 kW or 22 kW is technically cleaner wiring, but the extra install cost rarely pays back at home where the car sits overnight and a slower rate fills the battery just as reliably.
  2. See how long a charge takes. The power level this page gives you is the direct input to the EV charging time calculator, which models the taper curve above 80% and compares overnight versus rapid sessions.
  3. Price the charge session. Energy added times your home tariff. The EV charging cost calculator takes your battery size and the rate your wallbox runs at.
  4. Turn cost into cost per kilometre. The EV range and cost calculator divides energy by your real-world consumption so you can compare directly against petrol.
  5. Compare a full year against petrol. The EV vs petrol calculator puts your annual distance, home tariff and pump price into one number.
  6. Check a specific journey. The EV trip planner checks whether your range covers a route or whether a stop is needed.
  7. Lower the tariff by generating your own power. The solar panels for EV charging calculator sizes an array against your daily kilometres, which is the one move that reduces the tariff you enter in step 3.

Frequently Asked Questions

What size breaker do I need for a 7.4 kW home EV charger?

A 7.4 kW single-phase charger at 230 V draws 32 A continuously. The 125% continuous-load rule gives a design current of 40 A. The correct IEC breaker is the next standard size at or above 40 A, which is 40 A exactly. In practice many installers fit a 50 A breaker for a small margin, but 40 A is code-compliant if the cable is rated accordingly. For a 240 V UK installation the math is identical: 7680 W / 240 V = 32 A, design current 40 A, breaker 40 A.

What wire gauge is needed for a 22 kW three-phase EV charger?

A 22 kW three-phase charger at 400 V draws 22,000 / (sqrt(3) x 400) = 31.8 A per phase, rounded to 32 A rated. Design current at 125% = 40 A. Ampacity minimum: 6 mm² copper in conduit carries 40 A at 30 °C. For a 10 m run at 3% drop (400 V), the voltage-drop minimum is well below 1 mm², so ampacity governs. Use 6 mm² (AWG 10 equivalent) for most installations. For runs beyond 30 to 35 m, increase to 10 mm² to keep voltage drop inside the 3% limit.

Can I share the EV charger circuit with the garage sockets or garden lights?

No. A Mode 3 wallbox is classified as a continuous load under IEC 60364-7-722 and must have its own circuit breaker and cable from the consumer unit, carrying only the EV load. Adding garage sockets or any other load to the same breaker is not code-compliant: the combined current can exceed the breaker rating during a charging session, and the cable temperature will exceed its rating well before the breaker trips. Run a separate circuit for the wallbox, even if it means pulling a second cable to the garage.

How does cable run length affect the wire gauge I need?

Longer cable runs increase resistive voltage drop. For a 32 A charger at 230 V single-phase with 3% drop limit, the voltage-drop minimum for a 10 m run is about 2 mm² (well below the 6 mm² ampacity minimum, so ampacity governs). At 40 m, the voltage-drop minimum rises to about 7.9 mm², which exceeds 6 mm², so you would need 10 mm² to stay inside the drop limit. Enter your actual run length in the planner above for the precise threshold.

Is aluminium cable acceptable for a home EV charger circuit?

Aluminium is permitted by IEC 60364 for fixed wiring, but it is generally restricted to conductors 35 mm² and larger for branch circuits. For a typical 6 mm² EV charger circuit, copper is strongly preferred. Aluminium requires anti-oxidant compound at every termination, aluminium-rated connectors, and careful torque to prevent the cold-flow that causes loose connections over time. If aluminium is used, size at least one standard step larger than the copper equivalent, as aluminium carries roughly 78% of the same cross-section copper.

Methodology and sources

This planner sizes the breaker and cable for a home EV charging circuit. It treats every charger as a continuous load, applies the 125% design-current rule, then sizes the conductor to satisfy whichever is stricter: thermal ampacity or your chosen voltage-drop limit.

Reviewed and maintained by Rick Oosterling, who builds and wires 12 V, solar and EV systems hands-on. Last reviewed: June 2026. This is a planning aid, not a substitute for a qualified electrician or your local wiring and building code: a fixed EV charger circuit must be designed, installed and certified by a qualified professional.

Embed this tool

Use this planner on your own website. Copy the iframe code below.

Next steps in this workflow

Breaker and wire sized: verify the drop across your actual run, then check your panel capacity.