Copper conductor ampacity per NEC Table 310.16, breaker sizing limits, AWG to mm² cross-reference, and a quick circuit guide. Print it or save as PDF for the workshop wall.
| AWG size | 60 °C (TW) | 75 °C (THW / THWN) | 90 °C (THHN / XHHW-2) | mm² (approx) |
|---|---|---|---|---|
| 14 | 15 A | 20 A | 25 A | 2.1 |
| 12 | 20 A | 25 A | 30 A | 3.3 |
| 10 | 30 A | 35 A | 40 A | 5.3 |
| 8 | 40 A | 50 A | 55 A | 8.4 |
| 6 | 55 A | 65 A | 75 A | 13.3 |
| 4 | 70 A | 85 A | 95 A | 21.2 |
| 3 | 85 A | 100 A | 115 A | 26.7 |
| 2 | 95 A | 115 A | 130 A | 33.6 |
| 1 | 110 A | 130 A | 145 A | 42.4 |
| 1/0 | 125 A | 150 A | 170 A | 53.5 |
| 2/0 | 145 A | 175 A | 195 A | 67.4 |
| 3/0 | 165 A | 200 A | 225 A | 85.0 |
| 4/0 | 195 A | 230 A | 260 A | 107 |
Use the temperature column that matches the lowest-rated termination in the circuit. Most breakers and lugs are rated 75 °C, so the 75 °C column governs for typical residential and commercial work even when the wire insulation is rated 90 °C.
Aluminium carries roughly 78 percent of the same-size copper ampacity, so it is sized one to two AWG larger for the same load. Common 75 °C aluminium values: 8 AWG = 40 A, 6 AWG = 50 A, 4 AWG = 65 A, 2 AWG = 90 A, 1/0 = 120 A, 2/0 = 135 A, 4/0 = 180 A. For a full aluminium calculation, use the wire gauge calculator.
| AWG | Exact mm² | Nearest metric size | Typical use |
|---|---|---|---|
| 16 | 1.31 | 1.5 mm² | Lighting circuits, control wiring |
| 14 | 2.08 | 2.5 mm² | 15 A circuits, general outlets (US) |
| 12 | 3.31 | 4 mm² | 20 A outlets, kitchen and bathroom |
| 10 | 5.26 | 6 mm² | 30 A circuits, EV charger 7.4 kW |
| 8 | 8.37 | 10 mm² | 40 A circuits, EV charger 11 kW, ranges |
| 6 | 13.3 | 16 mm² | 55 A circuits, sub-panel feeds |
| 4 | 21.2 | 25 mm² | Sub-panels, large appliance feeds |
| 2 | 33.6 | 35 mm² | Service and feeder runs |
| 1/0 | 53.5 | 50 mm² | Main supply, generator feed |
| Circuit / load | Breaker | Minimum copper wire |
|---|---|---|
| Lighting, general 120 V | 15 A | 14 AWG |
| Outlets, kitchen, 120 V | 20 A | 12 AWG |
| Water heater, dryer feed | 30 A | 10 AWG |
| EV charger, 7.4 kW continuous | 40 A | 8 AWG |
| Electric range, 11 kW | 50 A | 6 AWG |
| Sub-panel feed, 100 A | 100 A | 3 AWG |
Continuous loads (EV chargers, motors, heaters running 3 hours or more) must be sized at 125 percent of the running current before reading the ampacity table. The values above already include that allowance.
Sharing or referencing this chart on your site, course or forum post? Copy a ready-made citation with the direct permalink.