CovertItAll.com
Wire gauge calculator

AWG Wire Ampacity Cheat Sheet

Copper conductor ampacity per NEC Table 310.16, breaker sizing limits, AWG to mm² cross-reference, and a quick circuit guide. Print it or save as PDF for the workshop wall.

Copper ampacity by AWG (NEC Table 310.16)

Allowable ampacity, copper, not more than three current-carrying conductors in a raceway or cable, 30 °C (86 °F) ambient.
AWG size60 °C (TW)75 °C (THW / THWN)90 °C (THHN / XHHW-2)mm² (approx)
1415 A20 A25 A2.1
1220 A25 A30 A3.3
1030 A35 A40 A5.3
840 A50 A55 A8.4
655 A65 A75 A13.3
470 A85 A95 A21.2
385 A100 A115 A26.7
295 A115 A130 A33.6
1110 A130 A145 A42.4
1/0125 A150 A170 A53.5
2/0145 A175 A195 A67.4
3/0165 A200 A225 A85.0
4/0195 A230 A260 A107

Use the temperature column that matches the lowest-rated termination in the circuit. Most breakers and lugs are rated 75 °C, so the 75 °C column governs for typical residential and commercial work even when the wire insulation is rated 90 °C.

Small-conductor breaker limit (NEC 240.4(D)). Regardless of the ampacity above, overcurrent protection for copper is capped at: 14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A. From 8 AWG up, size the breaker to the ampacity column.

Aluminium conductors

Aluminium carries roughly 78 percent of the same-size copper ampacity, so it is sized one to two AWG larger for the same load. Common 75 °C aluminium values: 8 AWG = 40 A, 6 AWG = 50 A, 4 AWG = 65 A, 2 AWG = 90 A, 1/0 = 120 A, 2/0 = 135 A, 4/0 = 180 A. For a full aluminium calculation, use the wire gauge calculator.

AWG to metric cross-reference

AWGExact mm²Nearest metric sizeTypical use
161.311.5 mm²Lighting circuits, control wiring
142.082.5 mm²15 A circuits, general outlets (US)
123.314 mm²20 A outlets, kitchen and bathroom
105.266 mm²30 A circuits, EV charger 7.4 kW
88.3710 mm²40 A circuits, EV charger 11 kW, ranges
613.316 mm²55 A circuits, sub-panel feeds
421.225 mm²Sub-panels, large appliance feeds
233.635 mm²Service and feeder runs
1/053.550 mm²Main supply, generator feed

Common circuit quick guide (copper, 75 °C)

Circuit / loadBreakerMinimum copper wire
Lighting, general 120 V15 A14 AWG
Outlets, kitchen, 120 V20 A12 AWG
Water heater, dryer feed30 A10 AWG
EV charger, 7.4 kW continuous40 A8 AWG
Electric range, 11 kW50 A6 AWG
Sub-panel feed, 100 A100 A3 AWG

Continuous loads (EV chargers, motors, heaters running 3 hours or more) must be sized at 125 percent of the running current before reading the ampacity table. The values above already include that allowance.

Derating reminder. Ampacity assumes 30 °C ambient and three or fewer conductors. Apply correction factors for higher ambient temperature (hot attics, roof spaces) and for four or more current-carrying conductors bundled in one raceway. When in doubt, go one size larger.
CovertItAll.com · AWG ampacity reference. Verify against the current NEC and local code before wiring. covertitall.com/printables/awg-ampacity.html Interactive wire gauge calculator →